Monterrey, Nuevo León Mon–Sat 10:00–18:00 (CST) (81) 4777 6921 (81) 2230 6079 info@creativeit.mx
Equipment sales

Fluke 1621 Soil Resistance Meter

Fluke 1621 soil resistance meter in Monterrey, Mexico for ground resistance and soil resistivity testing. 3-pole and 2-pole, 600 V CAT II.

Fluke 1621 Soil Resistance Meter

Want to make sure your grounding is effective? We have devices to measure soil resistance or soil resistivity. And soil resistance is essential for dissipating fault currents and preventing electrical hazards.

We have the Fluke 1621 kit, an easy-to-use earth ground tester. For earth resistance testing, the 1621 kit is the first line of defense for detecting reliable ground connections. The unit features basic ground test methods including 3-pole fall-of-potential tests and 2-pole earth resistance tests. Its convenient size, rugged case, and large, clear LCD make it an ideal field ground tester for most electrical grounding work environments. With a simple user interface and intuitive functionality, the Fluke 1621 kit is a practical grounding tool for electrical contractors, utility test engineers, and grounding specialists.

This device is crucial for evaluating the quality of the ground connection in electrical systems and for ensuring electrical safety

Key features

  • 3-pole fall-of-potential earth ground test for basic measurements
  • 2-pole resistance measurements for added versatility
  • Easily capture values with one-button operation
  • Ensure accurate measurements with automatic “noise” voltage detection
  • Hazardous voltage warning provides greater user protection
  • Clearly read and record data with a large backlit display
  • Hard carrying case
  • Rugged case and design for tough work environments
  • Portable size allows easy transport
  • Get instant alerts for measurements outside your set limit when using the adjustable limit setting
  • 600 V CAT II

General specifications

Measurement functions

3-wire earth ground resistance, conductor resistance in 2-wire AC systems, interference voltage

Intrinsic error

Indicates the reference temperature range and is guaranteed for one year

Measurement speed

2 measurements/second

Battery¹

One 9-volt alkaline battery (LR61)

Battery conditions

LO-BAT appears when the battery voltage drops below 6.5 V

Voltages

Between connectors H/C2 and E/C1:

250 Vrms maximum (effective voltage)

Between connectors S/P2 and E/C1

250 Vrms maximum

Climatic class

VDE/VDI 3540 RZ (complies with KWG per DIN 40040, 4/87)

Thermal characteristics²

Operation

-10 °C to +50 °C (+14 °F to +122 °F)

Operation

0 °C to +35 °C (+32 °F to +95 °F)

Storage

-20 °C to +60 °C (+68 °F to +140 °F)

Reference

+23 °C ±2 °C (+73 °F ±4 °F)

Temperature coefficient

±0.1 % of range per kelvin

Safety

IEC/EN 61010-1, 600 V CAT II, pollution degree 2

Dimensions

113 x 54 x 216 mm (4.5 x 2.1 x 8.5 in), including holster

Weight

850 g (1.9 lb), including standard accessories, approximate volume 600 cm³

Electrical specifications

Maximum deviations

E1 Influence factor

Load

E1 Deviation influence

0 %

E2 Influence factor

Supply voltage

E2 Deviation influence

0 %

E3 Influence factor

E3 Temperature

E3 Deviation influence

2.3 %

E4 Influence factor

Series interference voltage (20 V)

E4 Deviation influence

0.6 %

E5 Influence factor

Probe resistance and auxiliary probe resistance

E5 Deviation influence

10 %

Test voltage

3.7 kV

Protection type

IP 40; IEC/EN 60529

Electromagnetic compatibility

Emission

IEC/EN 61326 Class B

Immunity

IEC/EN 61326 Annex C

RE Resistance measurement

Measurement method

Voltage and current measurement with improved crosstalk attenuation, no measuring lead resistance compensation, with probe (3-wire) or without probe (2-wire), per IEC/EN 61557-5

Open-circuit voltage

23 to 24 V AC

Short-circuit current

> 50 mA AC

Measurement frequency

128 Hz

Maximum permissible overload

250 Vrms

Measurement time

8 seconds (average from pressing START)

Limit input

The tester retains the set value even if the instrument is switched off (assuming the battery power supply is sufficient)

Automatic resolution change

RH

< 7 kΩ

Resolution

0.01 Ω

RH

< 50 kΩ

Resolution

0.1 Ω

RH

> 50 kΩ

Resolution

1 Ω

DC + AC interference voltage display

V max.

30 Vrms

Common-mode rejection

> 80 dB at 50 Hz and 60 Hz

Ri

680 kΩ

Measurement uncertainty

< 10 % for pure AC and DC signals

Measuring range

0.15 Ω to 20 Ω

Resolution

0.01 Ω

Display range

0 to 19.99 Ω

200 Ω

Resolution

0.1 Ω

Display range

20 to 199.9 Ω

2 kΩ

Resolution

1 Ω

Display range

200 to 1999 Ω

Intrinsic uncertainty

±(6 % of measured value + 5D)

Operating uncertainty IEC 61557³

±(18 % of measured value + 5D)

Request a quote

Fluke 1621 Soil Resistance Meter

Send us the details and an engineer will get back to you today.

* Required fields
Message us on WhatsApp